Underground parking lots in apartment houses are becoming larger, more complex, and the risk of fires such as electric vehicle fires is increasing day by day. The following conclusions were reached by conducting an experiment to suggest an efficient smoke emission method that can be applied to apartments immediately and a smoke removal facility that needs to be applied to apartments to be built in the future. 1) The optimal smoke transfer method using a mobile blower to secure the visibility of the fire brigade in the early stages of the fire in an underground parking lot was found to be a mixed method (PPV+NPV) that combines positive and negative pressure smoke. 2) In the case of the mixed method (PPV+NPV), it may be difficult to install the blower at a height of 2m depending on the environment of the entrance and the conditions of each fire station. 3) The PPV method, which is most commonly used in the field, pushes air from the entrance of the underground parking lot to the blower or smoke exhaust lane. If there is no outlet nearby, smoke disturbance and eddy currents occur, which worsens the field of view, and smoke spreads to other areas, causing another damage. 4) It would be effective to apply the 27CMH/㎡ standard of the performance-oriented design evaluation and operation guideline such as fire fighting facilities.
목차
Abstract 1. 서론 2. 연구방법 2.1 실험환경 2.2 실험구성 및 방법 3. 실험결과 및 분석 3.1 1-1번 Case 3.2 1-2번 Case 3.3 2-1번 Case 3.4 2-2번 Case 3.5 2-3번 Case 4. 개선방안 5. 결론 참고문헌
화재의 과학적 감식, 원인규명 및 예방을 위한 학문과 기술의 발전을 도모하고, 산, 학, 연, 정의 상호 교류를 통한 화재예방과 조사 및 감식의 전문화와 함께 소방관련 정책방향 발전에 공한하며, 회원 및 화재 관련 분야의 국.내외 인사들과의 정보 교류를 위하여 설립되었다.
간행물
간행물명
한국화재감식학회 학회지 [Magazine of Fire Investigation Socity of Korea]