This paper reproduces the possibility of accidents and electric fires in the magnetic contactor(MC) of the control panel installed for the temperature control of the freezing warehouse, the low temperature warehouse and the storage. In addition, I would like to present a method for analyzing the characteristics and causes of accidents that occur due to an under voltage applied to a MC or an abnormal operation due to a foreign substance being interrupted. The inside of the control panel is composed of a molded-case circuit breaker(MCCB), a magnetic contactor(MC), a timer, and a terminal board. The MC for compressor and the MC for compressor control are designed to operate sequentially. The deterioration of the MC is caused by undervoltage and overvoltage, physical shock or vibration, inflow of foreign substances such as cockroaches and insects, formation of water or moisture. In other words, the inflow of foreign matter breaks the balance of the electromagnetic field of the MC and interferes with the formation of the magnetic path, so that heat and vibration are continuously generated and the function of the contact point is deteriorated. Therefore, in this paper, we analyze the ignition mechanism of MC and use it as fire detection data for the control panel for the refrigeration warehouse.
목차
Abstract 1. 서론 1.1 연구배경 및 목적 1.2 연구방향 2. 본론 2.1 화재 현황 및 화재사례 등 2.2 전자접촉기의 구조와 원리 2.3 전자접촉기 화재 위험성 실험 및 소손패턴 분석 2.4 연구결과 및 고찰 3. 결론 참고문헌
키워드
Magnetic ContactorDeteriorationUnder voltageOvervoltageShockHeatVibrationContact
화재의 과학적 감식, 원인규명 및 예방을 위한 학문과 기술의 발전을 도모하고, 산, 학, 연, 정의 상호 교류를 통한 화재예방과 조사 및 감식의 전문화와 함께 소방관련 정책방향 발전에 공한하며, 회원 및 화재 관련 분야의 국.내외 인사들과의 정보 교류를 위하여 설립되었다.
간행물
간행물명
한국화재감식학회 학회지 [Magazine of Fire Investigation Socity of Korea]