It is important to investigate cause and origin of fires to reduce damage and casualties. The difficulty of determining them has occurred because fires often destroy the key evidence. In this study, CFD-based Fire Dynamics Simulator (FDS) was used to reconstruct fire scene and presume origin of the Seomun market fire that occurred on November 30, 2016, in Daegu Metropolitan City. Comparing result of simulation with testimony of first witness and fire-fighters, it was estimated that the fire occurred outside of the market and sprinkler system worked. First-aid fire fighting was unsuccessful because of retardation of smoke detector activation. Fire-spreading into the building was delayed by the sprinkler system operation. And, it was found that tent covered on the stall accelerated fire spread.
목차
ABSTRACT 1. 서론 2. 사전정보 분석 및 화재모델링 2.1 사전정보 분석 2.2 발화지점 선정 및 경계조건 3. 실험결과 3.1 발화지점 : 건물내부 – Case 1 3.2 발화지점 : 건물외부 – Case 2 3.3 가판대 보호천막의 영향 4. 고찰 5. 결론 참고문헌
화재의 과학적 감식, 원인규명 및 예방을 위한 학문과 기술의 발전을 도모하고, 산, 학, 연, 정의 상호 교류를 통한 화재예방과 조사 및 감식의 전문화와 함께 소방관련 정책방향 발전에 공한하며, 회원 및 화재 관련 분야의 국.내외 인사들과의 정보 교류를 위하여 설립되었다.