This study investigates a fire incident involving a steam silencer at a cogeneration plant on February 28, 2023. The research aims to clarify the ignition mechanism caused by heat conduction between the steam silencer’s diffuser and roof finishing materials. The investigation included on-site inspections and two reenactment experiments. The first experiment confirmed that dry steam can reach temperatures exceeding 450°C under high pressure. The second experiment evaluated the heat accumulation of insulation, urethane foam, and waterproof sheets under 500°C conduction heat. Results revealed that while individual materials only carbonized, The combination of these roof finishing materials caused heat accumulation, leading to a temperature rise of up to 618.6°C.. The insulation and urethane foam acted as thermal barriers, causing internal heat accumulation that exceeded the heat source's temperature, ultimately igniting the waterproof sheet. To prevent recurrence, it is recommended that a “cooling space” be mandatory in the design of steam silencer installations to block direct heat conduction. Furthermore, a secondary safety review of design drawings by fire safety experts should be implemented.
목차
Abstract 1. 서론 1.1 연구 배경 및 목적 1.2 최근 7년간(2019~2025) 화재 통계분석 1.3 화재사례 1.4 화재 원인 분석 1.5 연구 범위 2. 이론적 고찰 2.1 화재현장 조사 2.2 열병합발전 구조 2.3 스팀(증기)의 특성[3] 2.4 배열회수보일러의 구조와 기능 2.5 스팀 사일런서의 구조 2.6 스팀 사일런서와 지붕 마감재 간 발화 가능성 3. 재현실험 3.1 실험목적 및 방법 4. 연구를 통한 개선 방안 제시와 연구공유를 통한 피드백(Feedback) 4.1 실험 결과에 따른 개선 방안 제시 4.2 연구결과의 공유를 통한 피드백(Feedback) 5. 결론 참고문헌
키워드
Steam silencerDiffuserRoof finishing materialCogeneration plantIgnition mechanism: Heat conductionHeat accumulationCooling space
화재의 과학적 감식, 원인규명 및 예방을 위한 학문과 기술의 발전을 도모하고, 산, 학, 연, 정의 상호 교류를 통한 화재예방과 조사 및 감식의 전문화와 함께 소방관련 정책방향 발전에 공한하며, 회원 및 화재 관련 분야의 국.내외 인사들과의 정보 교류를 위하여 설립되었다.
간행물
간행물명
한국화재감식학회 학회지 [Magazine of Fire Investigation Socity of Korea]