In order to reduce the cost of reinforcing the insulation of a building, it is sometimes finished with insulation in the building, and if a fall-down pattern occurs and the secondary ignition occurs, it can be mistaken for arson. In this study, a three-type fire model experiment was conducted with one control group to check whether the ceiling organic insulation finishing method contributes to the formation of the fall-down pattern and whether there is a difference in the characteristics found at the fire site by type of insulation. As a result of the experiment, all three types of experimental groups had high-temperature flaming droplets during the combustion expansion process, forming a fall-down pattern, and there were differences by type of insulation. This study shows that it is necessary to check whether the ceiling insulation is a material with flaming droplets at sites where a number of ignition points are identified but there are no other arson characteristics.
목차
Abstract 1. 서론 1.1 연구의 배경 1.2 연구의 목적 2. 본론 2.1 이론적 배경 2.2 화재사례 분석 및 검증 2.3 선행연구 검토 2.4 연구의 흐름 3. 화재재현 실험 3.1 화재재현 실험 3.2 (대조군) 천장 반자 내 유기질 단열재 화재 축소 모형실험 3.3 (실험군) 천장 유기질 단열 마감재 종류별 화재 축소 모형실험 4. 결론 4.1 연구의 요약 4.2 화재감식 착안사항 4.3 제도적 제언 참고문헌
화재의 과학적 감식, 원인규명 및 예방을 위한 학문과 기술의 발전을 도모하고, 산, 학, 연, 정의 상호 교류를 통한 화재예방과 조사 및 감식의 전문화와 함께 소방관련 정책방향 발전에 공한하며, 회원 및 화재 관련 분야의 국.내외 인사들과의 정보 교류를 위하여 설립되었다.
간행물
간행물명
한국화재감식학회 학회지 [Magazine of Fire Investigation Socity of Korea]