Recently, there has been a growing interested in prevention of hospital pollution. Virus and bacteria are transmitted this way by fine dust that exists in the air. In case microdust pass throughout inside human body, It could be fatal in elderly adults who have low level of immunity. Measuring microdust of medical institution located in Daegu Gyeongbuk area, We would like to find efficient management way of hospital facility. Using a particle counter Fluke-985 made by Fluke, We measured concentration of microdust in multiuse facility lobby, injection room, x-ray room, ward for each three hospital in primary, secondary and tertiary medical institution. The result of an experiment, lobby is the highest level in tertiary medical institution and x-ray room and ward are highest level in primary, secondary medical institution.