Most of the low-level liquid radioactive wastes generated from PWR plants are classified into high or low total suspended solid(HTDS or LTDS), and into radiochemical and radioactive laundry waste. Although the evaporation process has a high decontami- nation ability, it has several problems such as corrosion, foam, and congestion. A new liquid waste disposal process using the ion-exchange demineralizer(IED), instead of the current evaporation process, has been introduced into the Yonggwang NPP #5 and 6. These two methods have been compared to understand the differences in this study. Aspects compared here were the released radioactivity amount of the liquid radioactive wastes, the dose of off-site residents, the decontamination factor, and the amount of the solid radioactive wastes. The IED system is designed to discharge higher radioactivity about 20% than the evaporating system, and the actual radioactivity released from the evaporating and IED system were 0.473mCi and 1.098mCi, respectively. The radioactivity released from the IED was 2.32 times higher than that of the evaporating system. The dose of off-site residents was mSv for the evaporating system, and mSv for IED. The decontamination factor(DF) of the evaporator is, in most cases, far lower than the lower limits of detection(LLD) with the Ge-Li detector. Due to the low concentration of the liquid wastes collected from the liquid waste system, the decontamination factor of IED is very low. Since there is not enough data on the amount of solid radioactive wastes generated by the evaporation system, the comparison on these two systems has been conducted on the basis of the design, and the comparison result was that the evaporating system generated more wastes about 40% than IED.

목차

Abstract
 I. Introduction
 II. Treatment of Radioactive Liquid Waste.
  1. The Disposal in Korea and Overseas
  2. Characteristics
  3. Treatment Methods of Liquid Wastes
  4. Comparison and Analysis on the Effectiveness of Liquid Waste Treatments
 III. Conclusion
 IV. References

키워드

ion-exchange demineralizer(IED) evaporator liquid radioactive waste dose of off-site residents decontamination factor Treatment

저자

  • Yu-Sun Yeom [ 염유선 | 조선대학교 ]
  • Soong-Pyung Kim [ 김숭평 | 조선대학교 ]
  • Seung-Jin Lee [ 이승진 | 라드텍(주) ]

참고문헌

자료제공 : 네이버학술정보

간행물 정보

발행기관

  • 발행기관명
    한국방사성폐기물학회 [Korean Radioactive Waste Society]
  • 설립연도
    2003
  • 분야
    공학>원자력공학
  • 소개
    한국방사성폐기물학회는 국내 방사성폐기물 관리 분야 산ㆍ학ㆍ연 관계자들의 학술단체로 학술연구발표회 및 강연회 개최, 학술간행물 발간 등의 학술 진흥사업, 방사성폐기물에 관한 국제교류 및 협력 증진사업, 방사성폐기물에 관한 위탁연구 자문 및 평가사업 수행 등으로 국내 방사성폐기물 관리 분야 전반의 내부 역량 강화와 경쟁력 확보를 도모하고자 한다. 더 나아가 국가사회 발전에 미치는 중요성을 인식하는 계기를 만들고자 한다. 또한 이러한 활동을 통하여 국가경제 발전과 국민건강에 일조할 수 있도록 하며, 궁극적으로는 한국방사성폐기물학회가 세계 속의 학술단체로의 발전해 나가는 것을 목표로 한다.

간행물

  • 간행물명
    방사성폐기물학회지 [Journal of Nuclear Fuel Cycle and Waste Technology (JNFCWT)]
  • 간기
    계간
  • pISSN
    1738-1894
  • 수록기간
    2003~2017
  • 십진분류
    KDC 559 DDC 629

이 권호 내 다른 논문 / 방사성폐기물학회지 Volume 2 Number 3

    피인용수 : 0(자료제공 : 네이버학술정보)

    함께 이용한 논문 이 논문을 다운로드한 분들이 이용한 다른 논문입니다.

      페이지 저장