Fires in the fire switchboard are constantly occurring and efforts are being made to improve them. Most of the causes of fire in switchboards are due to poor contact at terminals, dust and water inflow. Among them, we have checked the possibility of fire caused by water inflow through fire cases, installation status, and combustion experiments. We have also confirmed that there are no specific criteria regarding electrical equipment, although the technical standards of the Ministry of Trade stipulate that “the structure would not allow water to permeate into the distribution box.” Therefore, this study warns of fire hazard caused by water inflow switchboard through the results of fire reproducibility experiment, and it expects that the supplementation of laws to improve the environmental factors that bring moisture into switchboard. We hope that the fire investigation will develop from the center of ignition source and factor to the center of fire prevention measures and contribute to fire prevention.
목차
Abstract 1. 서론 1.1 연구의 배경 및 목적 1.2 배전반 화재통계 및 분석 2. 이론적 배경 2.1 배전반의 정의 2.2 배전반 설치 규정 및 문제점 2.3 전기적인 발화요인 3. 배전반 화재 사례 및 설치 실태 3.1 화재 사례Ⅰ 3.2 화재 사례Ⅱ 3.3 배전반 설치 실태 4. 실험 결과 및 고찰 4.1 실험개요 4.2 실험내용 및 방법 4.3 재현실험 결과 및 고찰 4.4 재현실험 결과 분석 5. 결론 5.1 화재예방 및 제도개선 방안 참고문헌
화재의 과학적 감식, 원인규명 및 예방을 위한 학문과 기술의 발전을 도모하고, 산, 학, 연, 정의 상호 교류를 통한 화재예방과 조사 및 감식의 전문화와 함께 소방관련 정책방향 발전에 공한하며, 회원 및 화재 관련 분야의 국.내외 인사들과의 정보 교류를 위하여 설립되었다.
간행물
간행물명
한국화재감식학회 학회지 [Magazine of Fire Investigation Socity of Korea]