고분자 절연체의 가속열화에 따른 화학적특성 및 발화위험성에 관한 연구
A Study on Chemical Characteristics and Fire Risk according to the Accelerated Deterioration of the Polymer Insulator
In this paper, among the causes of electrical fires, the chemical properties due to thermal degradation of the wire coating, which is a polymer material, and the risk of ignition through temperature change by equivalent lifespan were analyzed. Insulated wires (HIV, 2.5SQ, single wire) used in small buildings under 500V were accelerated to deteriorate over time to produce samples for 0, 10, 20, 30, 40 years. Qualitative and quantitative analysis of insulators was performed using equipment such as strength, SEM, XRD, IR, TGA, and DSC. In addition, the temperature change by step above the allowable current was analyzed with an overcurrent tester, and through this, it was possible to confirm the risk of fire due to deterioration of insulation of old wires used in buildings. Through this study, it is possible to present the rationale for systematically introducing the replacement and repair period for old wires, and it is judged that it can be used as basic data for investigators to verify the cause of ignition due to insulation deterioration at the fire site.
목차
Abstract 1. 서론 1.1 연구의 배경 1.2 연구의 필요성 1.3 연구의 접근방법 2. 본론 2.1 이론적 고찰 2.2. 실험시료 제작 2.3 실험 분석 3. 결론 3.1 실험 결과 3.2 종합 의견 참고문헌
화재의 과학적 감식, 원인규명 및 예방을 위한 학문과 기술의 발전을 도모하고, 산, 학, 연, 정의 상호 교류를 통한 화재예방과 조사 및 감식의 전문화와 함께 소방관련 정책방향 발전에 공한하며, 회원 및 화재 관련 분야의 국.내외 인사들과의 정보 교류를 위하여 설립되었다.
간행물
간행물명
한국화재감식학회 학회지 [Magazine of Fire Investigation Socity of Korea]