In this paper, the current limiting characteristics of the transformer type superconducting fault current limiter (SFCL) with the two coupled secondary windings due to its winding direction were analyzed. To analyze the dependence of transient fault current limiting characteristics on the winding direction of the additional secondary winding, the fault current limiting tests of the SFCL with an additional secondary winding, wound as subtractive polarity winding and additive polarity winding, were carried out. The time interval of quench occurrence between two superconducting elements comprising the transformer type SFCL with the additional secondary winding was confirmed to be affected by the winding direction of the additional secondary winding. In case of the subtractive polarity winding of the additional secondary winding, the time interval of the quench occurrence in two superconducting elements was shorter than the case of the additive polarity winding.
목차
Abstract 1. INTRODUCTION 2. STRUCTURE AND OPERATIONAL PRINCIPLE 2.1. Structure and Mechanism 2.2. Experimental Apparatus 3. RESULT AND ANALYSIS 4. CONCLUSION ACKNOWLEDGMENT REFERENCES
키워드
Current limiting characteristicsTransformer type superconducting fault current limiter (SFCL)Coupled secondary windingsAdditional secondary windingWinding direction
저자
Tae Hee Han [ Jungwon University , Chungbuk, Korea ]
Sung Hun Lim [ Soongsil Uinversity, Seoul, Korea ]