To study the influence of woods on electric field distribution of 500kV EHV Transmission lines, the Solidworks software was applied to create the simplified model of 500kV transmission lines, and the ANSYS software based on finite-element method was applied to calculate space electric field intensity of transmission lines. This paper chooses the electric field intensity of transmission lines and span central cross section as the research object. The calculation result shows that the maximum electric field intensity is about 1808v/m without woods and 1916v/m with 12m high woods and 2055v/m with 16m high woods in the middle of the span cross section 20 meters high above the ground. Woods around transmission lines can distort the space electric field of lines, and the higher of woods, the larger of the maximum of electric field over the woods. And using the method of unmanned aerial vehicle (uav) carrying measuring instruments to measure the cases with woods and without wood, respectively, and compare which with the calculation results to find that results of analysis are in agreement with the experimental datas basicly.This paper studies the space electric field intensity distribution of transmission lines under different height and location of woods, such can provide preference for reasonable erection of 500kV EHV transmission lines.

목차

Abstract
 1. Introduction
 2. Fundamental Theory
  2.1. Governing Equation
  2.2. Theory of the Finite Element Method
  2.3. Model
 3. Finite Element Analysis
  3.1. Mesh
  3.2. Constraints and Boundary Conditions
 4. The Calculation of Space Distortion Electric Field Around Transmission Lines
  4.1. The Electric Field Distribution Around Transmission Lines without Tree
  4.2. The Effect of Trees on the Space Electric Field Around the Lines
  4.3. The Measurement of Electric Field Intensity Using Unmanned Aerial Vehicle with Electromagnetic Measurenment Instrument
  4.4. The Safe Distance between Trees and Lines
 5. Conclusions
 References

키워드

EHV transmission lines wood finite elements analysis ANSYS electric field distribution

저자

  • Fugen Song [ College of Electrical Engineering and Automation Fuzhou University, Fuzhou, China ]
  • Han Lin [ Fujian Electrical Power Company Limited, Fuzhou, China ]
  • Sheng Lan [ College of Electrical Engineering and Automation Fuzhou University, Fuzhou, China ]

참고문헌

자료제공 : 네이버학술정보

간행물 정보

발행기관

  • 발행기관명
    보안공학연구지원센터(IJGDC) [Science & Engineering Research Support Center, Republic of Korea(IJGDC)]
  • 설립연도
    2006
  • 분야
    공학>컴퓨터학
  • 소개
    1. 보안공학에 대한 각종 조사 및 연구 2. 보안공학에 대한 응용기술 연구 및 발표 3. 보안공학에 관한 각종 학술 발표회 및 전시회 개최 4. 보안공학 기술의 상호 협조 및 정보교환 5. 보안공학에 관한 표준화 사업 및 규격의 제정 6. 보안공학에 관한 산학연 협동의 증진 7. 국제적 학술 교류 및 기술 협력 8. 보안공학에 관한 논문지 발간 9. 기타 본 회 목적 달성에 필요한 사업

간행물

  • 간행물명
    International Journal of Grid and Distributed Computing
  • 간기
    격월간
  • pISSN
    2005-4262
  • 수록기간
    2008~2016
  • 십진분류
    KDC 505 DDC 605

이 권호 내 다른 논문 / International Journal of Grid and Distributed Computing Vol.9 No.10

    피인용수 : 0(자료제공 : 네이버학술정보)

    함께 이용한 논문 이 논문을 다운로드한 분들이 이용한 다른 논문입니다.

      페이지 저장