To deal with the faulted line selection in the single-phase to ground faults caused by neutral non-effective grounding in the distribution network, a new method by using zero-sequence admittance is proposed in this paper. Compensation admittance, which amplifies the difference in zero-sequence admittance between the faulted line and the unfaulted line, is convenient for the formation of the criteria for value setting in engineering. To eliminate the blind zone, combining the criterion of the susceptance error in the compensated admittance with the phase angle criterion helps form a new algorithm to identify the single-phase to ground faults in the neutral non-effectively grounded system. Results of simulation tests show that the algorithm has nothing to do with the network structure and parameters, fault conditions and fault resistance, significantly escalating the successful selection of the faulted line.
목차
Abstract 1. Introduction 2. The Principle for the Algorithm of Zero-sequence Admittance Line Selection 3. The Grounded Protection with Zero-sequence Compensated Admittance 3.1. Protection Principle 3.2. Protection Setting 3.3. Simulation Study 4. Conclusion References
보안공학연구지원센터(IJSIA) [Science & Engineering Research Support Center, Republic of Korea(IJSIA)]
설립연도
2006
분야
공학>컴퓨터학
소개
1. 보안공학에 대한 각종 조사 및 연구
2. 보안공학에 대한 응용기술 연구 및 발표
3. 보안공학에 관한 각종 학술 발표회 및 전시회 개최
4. 보안공학 기술의 상호 협조 및 정보교환
5. 보안공학에 관한 표준화 사업 및 규격의 제정
6. 보안공학에 관한 산학연 협동의 증진
7. 국제적 학술 교류 및 기술 협력
8. 보안공학에 관한 논문지 발간
9. 기타 본 회 목적 달성에 필요한 사업
간행물
간행물명
International Journal of Security and Its Applications
간기
격월간
pISSN
1738-9976
수록기간
2008~2016
등재여부
SCOPUS
십진분류
KDC 505DDC 605
이 권호 내 다른 논문 / International Journal of Security and Its Applications Vol.9 No.2