Seokho Nam, Woo Seung Lee, Jiho Lee, Young Jin Hwang, Tae Kuk Ko
언어
영어(ENG)
URL
https://www.earticle.net/Article/A212567
※ 기관로그인 시 무료 이용이 가능합니다.
※ 학술발표대회집, 워크숍 자료집 중 4페이지 이내 논문은 '요약'만 제공되는 경우가 있으니, 구매 전에 간행물명, 페이지 수 확인 부탁 드립니다.
4,000원
원문정보
초록
영어
Smart fault current controller (SFCC) proposed in our previous work consists of a power converter, a high temperature superconducting (HTS) DC reactor, thyristors, and a control unit [1]. SFCC can limit and control the current by adjusting firing angles of thyristors when a fault occurs. SFCC has complex structure because the HTS DC reactor generates the loss under AC. To use the DC reactor under AC, rectifier that consists of four thyristors is needed and it increases internal resistance of SFCC. For this reason, authors propose a hybrid type superconducting fault current limiter (SFCL). The hybrid type SFCL proposed in this paper consists of a non-inductive superconducting coil and two thyristors. To verify the feasibility of the proposed hybrid type SFCL, simulations about the interaction of the superconducting coil and thyristors are conducted when fault current flows in the superconducting coil. Authors expect that the hybrid type SFCL can control the magnitude of the fault current by adjusting the firing angles of thyristors after the superconducting coil limits the fault current at first peak.
목차
Abstract 1. INTRODUCTION 2. OPERATING PRINCIPLE 3. SFCL DESIGN AND SIMULATION SETUP 3.1. Resistive Type Superconducting Coil 3.2. Thyristor Control Circuit 3.3. Simulation Setup 4. SIMULATIONS AND ANALYSIS 5. CONCLUSION ACKNOWLEDGMENT EXAMPLE REFERENCES