The output current of grid-connected PV inverters should not excess harmonic contents. Also, because they are driven connected with grid, the reliability of electric power’s quality should be secured. But, the current controllers of the grid-connected PV inverter decrease the electric power’s quality due to not considering the harmonic contents of the output current. This paper proposed the current controllers of the grid-connected PV inverters to supplement the decrease of the electric power’s quality because of the harmonic contents of the electric power’s quality and the harmonic contents of the output current. The proposed current controllers controlled the harmonic contents of the output current by controlling gains of the current controllers in consideration of the harmonic contents of the output current. As a result, when total harmonic distributions of the grid voltage were 0.4% and 4.1%, the excellence of the proposed current controllers was shown through the experience, by obtaining excellent results of being controlled low as the total harmonic distributions of the output current were 0.756% and 0.78% respectively.
목차
Abstract 1. Introduction 2. Grid-connected PV Inverter 2.1. Maximum Power Point Tracking (MPPT) 2.2. Phase Locked Loop 3. Discrete Fourier Transform (DFT) 4. Proposed Output Current Controller of Inverter 4.1. Conventional Current Controller of Inverter 4.2. Proposed Current Controller of Inverter 5. Experimental Results and Discussion 6. Conclusion Acknowledgements References
보안공학연구지원센터(IJCA) [Science & Engineering Research Support Center, Republic of Korea(IJCA)]
설립연도
2006
분야
공학>컴퓨터학
소개
1. 보안공학에 대한 각종 조사 및 연구
2. 보안공학에 대한 응용기술 연구 및 발표
3. 보안공학에 관한 각종 학술 발표회 및 전시회 개최
4. 보안공학 기술의 상호 협조 및 정보교환
5. 보안공학에 관한 표준화 사업 및 규격의 제정
6. 보안공학에 관한 산학연 협동의 증진
7. 국제적 학술 교류 및 기술 협력
8. 보안공학에 관한 논문지 발간
9. 기타 본 회 목적 달성에 필요한 사업
간행물
간행물명
International Journal of Control and Automation
간기
월간
pISSN
2005-4297
수록기간
2008~2016
십진분류
KDC 505DDC 605
이 권호 내 다른 논문 / International Journal of Control and Automation Vol.6 No.5