The purpose of this study is analysis about cooling load saving of heat absorbing glass window. The process of this study is as follows. First, it prepares two test room of the identical area and the Volume. One installed heat absorbing glass window and different one installed the general transparent glass window. And it maintains the both test room with 26℃, it measured and compared operation cooling energy consumption of both test room which it follows in solar radiation gain through installed window. The energy saving ratio of heat absorbing window expressed about 4.5 ~ 8% under range of outdoor teperature was from 23.8℃ to 31.3℃.