초록

영어
In this study, a seismic capacity of isolated electrical cabinet system was evaluated through shaking table test. A high voltage Vacuum Contactor Breaker (VCB) was selected, and developed seismic isolation system, which is consisted of 4 damper and 10 scattered ball-caster, for electrical cabinet. Damper was to resist lateral force, and ball-casters absorbed vertical shock energy due to up-lift. Ground motion was adjusted to the spectrum defined from Korean seismic test method for telecommunication facilities. To evaluate seismic behavior of specimen, three dimensional accelerations were measured at three points of cabinet system. The dynamic amplification factors are ranged from 0.83 to 4.19, which is lower than that analysed in prior research. Because of the light weight of cabinet, overall behavior is governed by overturning and induced large up-lift behavior was monitored during the excitation. Maximum lateral drift of slender side of cabinet exceed 75mm which is allowed maximum lateral drift in KS standard, but large lateral drift is due to rocking behavior of cabinet. So, the cabinet can maintain its function after two times of excitation.

목차

Abstract
1. 서론
2. 수배전반의 지진거동
2.1 횡력에 대한 거동
2.2 내진성능 평가기준
3. 실험체 개요
3.1 수배전반의 개요
3.2 지진격리장치의 개요
4. 실험 개요
4.1 실험장치 및 실험절차
4.2 실험세팅과 계측
4.3 실험방법
5. 실험 결과
5.1 공진실험
5.2 지진실험
6. 결론
REFERENCES

저자

  • 고동우 [ Ko, Dong-Woo | 제주대학교, 건축학부, 부교수 ] Corresponding Author

참고문헌

자료제공 : 네이버학술정보

    간행물 정보

    • 간행물
      대한건축학회연합논문집 [Journal of the Regional Association of Architectural Institute of Korea]
    • 간기
      격월간
    • pISSN
      1229-5752
    • 수록기간
      1999~2026
    • 등재여부
      KCI 등재
    • 십진분류
      KDC 540 DDC 690