Earticle

다운로드

전열교환 환기장치의 급배기 풍량비에 따른 결로방지 방안의 제안
A Proposal of Condensation Prevention Method in the Heat Recovery Ventilation System according to the Supply & Exhaust Air Flow Ratio

  • 간행물
    대한건축학회연합논문집 KCI 등재 바로가기
  • 권호(발행년)
    제19권 제6호 통권 82호 (2017.12) 바로가기
  • 페이지
    pp.165-172
  • 저자
    김동석, 김종원, 이정재
  • 언어
    한국어(KOR)
  • URL
    https://www.earticle.net/Article/A321112

원문정보

초록

영어
The element core which is really conduct heat exchange is a important component of the heat recovery ventilation system. When it is polluted and destroyed by condensation, polluted air is flowing into indoor and heat exchange rate is decrease. But the element core was not included in condensation detected range. This study was conducted to examine the applicability of condensation prevention according to the supply & exhaust air flow ratio control without additory equipment configuration. Experiments was conducted to the supply & exhaust air flow ratio 1.0:1.0 to 1.0:2.5 in winter outside temperature(-6.0℃ to -15.0℃) and condensation of the element core was judged with the hydrochromic detection sheet. The hydrochromic detection sheet was made by the hydrochromic ink which is changed the color when it contact water, the hydrochromic detection sheet could detect condensation in the element core which could be not detect by naked eyes. As a result, as the supply & exhaust air flow ratio increased, the condensation decreased. The lower outside temperature, the larger the supply & exhaust air flow ratio which was required to prevent condensation. In order to raise applicability of the supply & exhaust air flow ratio control, the study configured exhaust air temperature(the minimum exhaust air temperature 2.5℃ when condensation was not occured) as control criterion and established a control algorithm. Because heat exchange rate and condensation occur condition are changed according to the material and form of element core, In order to generalization of this algorithm, It is necessary to classify element core by property and conduct various experiments.

목차

Abstract
 1. 서론
  1.1 연구배경 및 목적
  1.2 연구범위 및 방법
 2. 전열교환 환기장치의 결로
  2.1 전열교환 환기장치
  2.2 전열교환 환기장치 결로판정의 범위
  2.3 전열교환 환기장치 결로방지 방안
 3. 실험 방법
  3.1 급·배기 풍량비 제어 운전
  3.2 엘리먼트코어의 결로 판정
 4. 실험 결과
  4.1 급·배기 풍량비에 따른 결로발생
  4.2 급·배기 풍량비 제어기준
  4.3 급·배기 풍량비 제어 알고리즘 구축
 5. 결론
 REFERENCES

저자

  • 김동석 [ Kim, Dong-Seok | 동아대학교 건축공학과, 석사과정 ]
  • 김종원 [ Kim, Jong-Won | 동아대학교 건축공학과, 박사과정 ]
  • 이정재 [ Yee, Jurng-Jae | 동아대학교 건축공학과 교수, 공학박사 ] Corresponding author

참고문헌

자료제공 : 네이버학술정보

    간행물 정보

    • 간행물
      대한건축학회연합논문집 [Journal of the Regional Association of Architectural Institute of Korea]
    • 간기
      격월간
    • pISSN
      1229-5752
    • 수록기간
      1999~2026
    • 등재여부
      KCI 등재
    • 십진분류
      KDC 540 DDC 690