사무소건물에서 정풍량 방식과 변풍량 방식 적용에 따른 냉방에너지 소비 특성에 관한 분석
A Study on Characteristics of the Cooling Energy Consumption by CAV and VAV HVAC system in Office Building
The energy saving of HVAC that is the occupiest on office building is being more important. In office building, CAV and VAV are adopted very much. Therefore, on this paper, we compared with VAV and CAV focused on energy consumption by using dynamic energy simulation. For objective comparison, after we chose standard building, found building that is closed to our standard building, we simulated. During seasonal cooling period June, July, August, September, the result of CAV and VAV energy uses were 34969.44kwh/m² and 27212.77kwh/m². Baesd on this result, we could find VAV is more energy effective as much as 7756.68kwh/m² than CAV.
목차
Abstract 1. 서론 1.1 연구의 목적 2. AHU(공조기)와 열원 모델링 2.1 AHU(공조기) 모델링 2.2 냉방열원 모델링 3. 시뮬레이션 결과 4. 결론 참고문헌