변풍량 라인디퓨져가 적용된 사무소 건물에서 실내온도와 기류분포에 대한 실험 및 CFD 시뮬레이션
Experiments & CFD Simulation of Indoor Temperature and AirFlow Distribution in the Office Building applied by V.A.V Line Diffuser
The purpose of this study is to review the reliability of the CFD. To perform this study, CFD simulations were compared with experimental results based on the performance results of the diffuser line. The results of this study are as follows. 1) Looking at the results of indoor air distribution measurements, Air distribution of indoor through Air of diffuser could judge to be distributed of indoor air evenly. 2) It compared actual data of Cooling experimental and heating experimental with the CFD analysis results. the average error rate of Cooling was 6% and the average error rate of Heating was 6.9%. In air flow case, the air velocity is some different to 0m/s ~ 0.178m/s. Looking at the air flow and the air velocity, two results could judge to be similar to pattern. As a result, the predictions of the indoor thermal and airflow environment through CFD simulation are considered possible.